Q: Dat P0 e P9 di prœuf, cuma calculo l’eficienza a diferenti livei de carich?
A: Eficienza η=P_fuora / (P_fuora + P0 + 2 × P6) × 100%, induè=fatur de carich.
Esempi: trasformadur 10 MVA, P0=12 kW, P6=85 kW:
|
Careg |
|
Salida (kW) |
P0 (kW) |
2×P6 (kW) |
η (%) |
|
25% |
0.25 |
2,500 |
12 |
5.3 |
99.31 |
|
50% |
0.50 |
5,000 |
12 |
21.3 |
99.34 |
|
75% |
0.75 |
7,500 |
12 |
47.8 |
99.21 |
|
100% |
1.00 |
10,000 |
12 |
85.0 |
99.04 |
|
120% |
1.20 |
12,000 |
12 |
122.4 |
98.89 |
Eficienza massima a=√(P0 / P6)=0.376 → ~37,6% de carich.
Norme de eficienza energètica:
• CIC 60076-20: class AEE A (püsee volt) → D.
• Ecoprogetaziun UE 2019/1783: Livel 2 (2021), Livel 3 (2025-27).
• DOE 10 CFR Part 431: nœuva norma en vigur giugn 2026.
• Regn Ünì 20052-2020 (Cina): Grado 1 (püsee volt) → 3.
• IS 1180 (India): valutaziun stellar BEE 1-5.
Aprocc TCO: TCO=Prezi + A × P0 + B × P9
Un ≈ 3.000–8.000 $/kW (nissun cust capitalizà de carich).
B ≈ 500-2.000 $/kW (cust capitalizà del carich).